Power Quality Solutions

We specialize in conducting detailed system studies and PQS measurements, adhering to IEEE-519 standards. Our team collects power quality parameters and analyzes the data to create customized systems for each project. We provide online monitoring services through an advanced analytics portal to ensure optimal performance post-installation. Our personalized approach sets us apart as a professional and client-centered service provider, catering to the unique requirements of industries and utility companies.

We provide an extensive selection of Power Quality Solutions, with tailor-made options available for Reactive Power Management. By implementing advanced technology and process enhancements, we have consistently delivered successful results in minimizing various losses for our clients. Committed to delivering comprehensive solutions, we are devoted to meeting all power quality requirements with utmost efficiency.

APIL's Core Expertise

MV Capacitor Banks

MV Capacitor Banks

For utility-connected substations ensuring grid-level stability

LV Capacitor Banks

LV Capacitor Banks

Internal distribution optimisation and loss reduction

APFC Systems

APFC Systems

Automatic Power Factor Correction with real-time monitoring

Integrated Protection

Integrated Protection

Integration with monitoring, redundancy, and protection architectures

Active Power Conditioning Panels

Active Power Conditioning Panels

Engineered for UPS-heavy, power-electronics-dominated environments

APIL Core Expertise

Passive Harmonic Filters

Passive Harmonic Filters
  • Single Tuned Filter
  • High Pass Filter
  • C-Type Filter

Power Quality Solutions

Specifications

  • Nominal Voltage: 3.3kV, 6.6kV, 12 kV, 33kV
  • 50 Hz / 60 Hz • Step Configuration: As per customer’s requirement
  • Protection: HRC Fuses
  • Reactor: As per customer’s requirement (No reactor / 0.2 % / 6%)
  • Switching: Vacuum Contactor • Single / Double star with RVT or NCT protection
  • Indoor / Out-Door version

Specifications

  • Normal Voltage 440 Volts, 3 Phase, 50 Hz / 60 Hz Protection class: IP 4X / 5X
  • Cooling: Self-convection (take care of sufficient convection)/Forced Cooling
  • Reactor: As per customer’s requirement (No reactor / 0.2 % / 7% or 14 %)
  • Switching: Contactor switched OR Thyristor switch (TSM)
  • Using our TSM modules, we can give APFC panel with 1kVAr Resolution for Dynamic Fast Fluctuating Load
  • Combination of Static Var Generator (SVG) + Active Harmonic Filter (AHF) for most effective harmonic filtering and power factor improvement

Specifications

  • Normal Voltage 440 Volts, 3 Phase, 50 Hz / 60 Hz Protection class: IP 4X / 5X
  • Cooling: Self-convection (take care of sufficient convection)/Forced Cooling
  • Reactor: As per customer’s requirement (No reactor / 0.2 % / 7% or 14 %)
  • Switching: Contactor switched OR Thyristor switch (TSM)
  • Using our TSM modules, we can give APFC panel with 1 kVAr Resolution for Dynamic Fast Fluctuating Load
  • Combination of Static Var Generator (SVG) + Active Harmonic Filter (AHF) for most effective harmonic filtering and power factor improvement

Specifications

  • Customized Power Control / Motor control/ Variable Frequency Drive Panels are manufactured as per the customer’s requirement
  • Normal Voltage 440 Volts, to 33 kV
  • 3 Phase 4 wire / 3 phase 3 wire
  • 50 Hz / 60 Hz
  • Protection class: IP 4X / 5X
  • Cooling: Self-convection (take care of sufficient convection)/Forced Cooling

Specifications

  • Active Harmonic Filters (AHF) and Static Var Generators (SVG)
  • Normal Voltage 400 Volts, to 590 Volts
  • 3 Phase 4 wire / 3 phase 3 wire
  • 50 Hz / 60 Hz
  • Protection class: IP 4X / 5X
  • Cooling: Self-convection (take care of sufficient convection)/Forced Cooling

Specifications

  • Outdoor / indoor application
  • Rated voltage: 3.3kV / 6.6 /11 kV at 50 Hz
  • Rated current: 400 A
  • Rated Capacitor switching current: 100/200A
  • Rated short-time current: 10 kA rms for 1 sec
  • Electrical / Mechanical endurance: 1,00,000 operations

Specifications

  • Indoor / Indoor application
  • Rated voltage: 3.3kV / 6.6 /11 kV at 50 Hz
  • Rated current: 400 A
  • Rated Capacitor switching current: 100/200 A
  • Rated short-time current: 10 kA rms for 1sec
  • Electrical / Mechanical endurance:100000 operations

Specifications

  • In door / In door application
  • Rated voltage: 11 kV at 50 Hz
  • Rated current: 1250 A
  • Rated short circuit peak withstand current:37.5 kA rms for 1 sec
  • Rated power frequency with voltage – 75 kV peak
  • Electrical / Mechanical endurance: 50,000 . 10,000 operations

Current Transformer

APIL’s Current transformers are designed for medium-voltage metering and protection applications, offering durability, insulation reliability, and compliance with IS/IEC standards. It is commonly used in metering cubicles, power distribution panels which are used in substations, industrial power networks, utilities, and protection schemes.

Key Features

  • Suitable for system voltages up to 33 kV (depending on design and application).
  • Available in Resin Cast and indoor or outdoor constructions.
  • Multicore CT provides different ratios and uses for different applications.
  • Provides Metering, monitoring and Protection cores available to use with meter and relay operation.
  • Accuracy classes available for both Protection (3P/6P) and Metering (0.2/1.0) applications.
  • Maintain precise ratio and phase angle for reliable metering and billing, especially in utility and industrial applications
  • Weatherproof construction with IP55/IP65 enclosure options for outdoor installations.
  • Provides excellent insulation, mechanical strength, and moisture resistance.
  • Provide galvanic isolation between high-voltage circuits (Primary) and low-voltage (secondary) measuring or control equipment ensuring safety of operator.

Principle of Operation

These CTs are step down high primary currents (hundreds or thousands of amps) to a safe, measurable level (1 A or 5 A) for meters and instruments. CTs are supply accurate current signals to protective relays, enabling them to detect faults like overloads, short circuits, or earth fault by sensing current from primary side.

Typical Applications

  • Metering cubicles for energy monitoring in substations and industrial plants.
  • Protection relays in switchgear or control panels.
  • Substation protection schemes.
  • Generator and transformer backup protection.
  • Monitoring load current for system optimization.
  • Scada integration for remote supervision and control.

Technical Specification

Parameter Specification
System Voltage 3.3 kV, 6.6 kV, 11 kV, 22 kV, 33 kV
Frequency 50 Hz
Secondary Voltage 110 V
Construction Resin Cast indoor or outdoor
Standards IS 2705:1992, IEC 61869-1 & IEC 61869-2
Accuracy Class 0.2, 0.5, 1.0, 3P, 6P
Protection Level Up to 170 kVp BIL
Installation Indoor / Outdoor

APIL Value Proposition

The CT manufactured by Akanksha Power & Infrastructure Ltd. combines excellent insulation, mechanical strength, and moisture resistance and maintain precise ratio and phase angle for reliable metering and billing, especially in utility and industrial applications

Marketing Pitch

"APIL's Current Transformer (CT) provides galvanic isolation between high-voltage circuits (Primary) and low-voltage (secondary) measuring or control equipment with high accuracy, precise ratio and phase angle ensuring safety of operator up to 33 kV."

Voltage Transformer

APIL’s Voltage transformers/Potential transformers are designed for medium-voltage metering and protection applications, offering durability, insulation reliability, and compliance with IS/IEC standards. It is commonly used in metering cubicles, power distribution panels which are used in substations, industrial power networks, utilities, and protection schemes.

Key Features

  • Suitable for system voltages up to 33 kV (depending on design and application).
  • Available in Resin Cast and indoor or outdoor constructions which are maintenance free, compact & durable.
  • Multicore PT provides uses for different applications.
  • Provides Metering, monitoring and Protection cores available to use with meter and relay operation as well as use as aux. control supply source.
  • Accuracy classes available for both Protection (3P/6P) and Metering (0.2/1.0) applications.
  • Maintain precise ratio and phase angle for reliable metering and billing, especially in utility and industrial applications
  • Weatherproof construction with IP55/IP65 enclosure options for outdoor installations.
  • Provides excellent insulation, mechanical strength, and moisture resistance.
  • Provide galvanic isolation between high-voltage circuits (Primary) and low-voltage (secondary) measuring or control equipment ensuring safety of operator.

Principle of Operation

These PTs are step down high primary voltages (hundreds or thousands of volts) to a safe, measurable level (110V) for meters and instruments. PTs are supply accurate voltage signals to protective relays, enabling them to detect faults like under voltage, over voltage, negative sequence voltage fault by sensing voltage from primary side.

Typical Applications

  • Metering cubicles for energy monitoring in substations and industrial plants.
  • Protection relays in switchgear or control panels.
  • Substation protection schemes.
  • Generator and transformer backup protection.
  • Monitoring voltage for system optimization.
  • Scada integration for remote supervision and control.

Technical Specification

Parameter Specification
System Voltage 3.3 kV, 6.6 kV, 11 kV, 22 kV, 33 kV
Frequency 50 Hz
Secondary Voltage 110 V
Construction Resin Cast indoor or outdoor
Standards IS 3156, IEC 61869-3, IEC-60044
Accuracy Class 0.2, 0.5, 1.0, 3P, 6P
Protection Level Up to 170 kVp BIL
Installation Indoor / Outdoor

APIL Value Proposition

The VT manufactured by Akanksha Power & Infrastructure Ltd. combines excellent insulation, mechanical strength, and moisture resistance and maintain precise ratio and phase angle for reliable metering and billing, especially in utility and industrial applications

Marketing Pitch

"APIL's Voltage Transformer (VT) provides galvanic isolation between high-voltage circuits (Primary) and low-voltage (secondary) measuring or control equipment with high accuracy, precise ratio and phase angle ensuring safety of operator up to 33 kV."

Residual Voltage Transformer

APIL's Residual Voltage Transformer (RVT) is a specialized voltage transformer designed for detecting earth faults, neutral displacement, and zero-sequence (residual) voltage in medium-voltage power systems. It is primarily used in substations, industrial power networks, utilities, and protection schemes where accurate ground-fault detection is essential.

Key Features

  • Suitable for system voltages up to 33 kV (depending on design and application).
  • Available in Resin Cast (Indoor/Outdoor) and Oil-Cooled Outdoor constructions.
  • Uses a 3-Phase, 5-Limb CRGO Core to avoid magnetic saturation during earth faults.
  • Provides a Residual (Tertiary) Open-Delta (V-V) Winding for zero-sequence voltage detection.
  • Accuracy classes available for both Protection (3P/6P) and Metering (0.5/1.0) applications.
  • Weatherproof construction with IP55/IP65 enclosure options for outdoor installations.
  • Optional ferro-resonance suppression resistors for improved system reliability.

Principle of Operation

During normal system operation, the vector sum of the three phase voltages is nearly zero. When a single-phase-to-earth fault occurs, a residual voltage develops. The RVT detects this residual voltage through its open-delta winding and supplies the signal to protection relays such as:

  • 59N – Neutral Overvoltage Relay
  • 64 – Ground Fault Protection Relay
  • Directional Earth Fault Relays (DEF)

Typical Applications

  • Earth fault detection in ungrounded and resonant-grounded systems.
  • Neutral displacement monitoring.
  • Substation protection schemes.
  • Generator and transformer backup protection.
  • Zero-sequence voltage measurement.
  • Voltage indication during maintenance and line isolation.

Technical Specification

Parameter Specification
System Voltage 3.3 kV, 6.6 kV, 11 kV, 22 kV, 33 kV
Frequency 50 Hz
Secondary Voltage 110 V / 190 V
Construction Resin Cast / Oil Cooled
Standards IEC 61869-3, IS 3156, IS 2705
Accuracy Class 0.5, 1.0, 3P, 6P
Protection Level Up to 170 kVp BIL
Installation Indoor / Outdoor

APIL Value Proposition

The RVT manufactured by Akanksha Power & Infrastructure Ltd. combines robust 5-limb core design, high insulation reliability, and utility-grade protection performance. It is suitable for utilities, transmission companies, DISCOMs, renewable energy plants, and industrial substations requiring dependable earth-fault monitoring and protection.

One-Line Marketing Pitch

"APIL's Residual Voltage Transformer (RVT) provides precise zero-sequence voltage detection for reliable earth-fault protection, ensuring enhanced safety, system stability, and uninterrupted power supply in medium-voltage networks up to 33 kV."

Specifications

  • CT – PT for system voltage up to 33 kV Ip up to 1250
  • A Burden & Accuracy class as per IS2705, IEC- 60044
  • Conformance to other standards on request
  • Outdoor Cycloaliphatic Resin cast CT-PT for system voltage up to 33 kV Ip up to 1250

FILM CAPACITOR

Shunt Reactive Power

APIL’s film capacitor is suitable for shunt reactive power compensation. This can be used in fixed/switched capacitor banks indoor/outdoor, in series with or without damping/ de-tuned/ tuned reactors. This capacitor is APP (All Polypropylene) type non-self-healing and oil impregnated.

Key Features

  • Capacitor single unit is designed up to 1100kVAr and up to 40kV.
  • Customized design configuration available 1-Φ/1B, 1-Φ/2B, 3-Φ/Δ/3B, 3Φ/Y/3B, 3Φ/Y/4B.
  • Tan delta (at 50Hz.) ≤ 2 x 10-4 and losses are ≤0.2W/kVAr
  • Self-Discharge time 300sec/600sec with residual voltage 50/75 Volts using internal discharge resistors.
  • Provided with external or internal fuse design as per requirement.
  • Suitable for long duration over voltages up to 130% and current of 1.3 times rated current.
  • Non-Self-healing design with oil impregnated.
  • Natural air-cooled design and temperature category up to -40/D.
  • Container of capacitor units available both in CRCA or stainless steel.
  • Special stainless steel earthing brackets provided on both ends to ensure proper earthing & safety.
  • Suitable for indoor and outdoor applications.

Principle of Operation

A shunt power capacitor operates on a simple principle: it supplies leading reactive power to counteract the lagging reactive power of inductive loads (like motors and transformers). By doing so, it improves the system's power factor, stabilizes voltage, and reduces transmission losses.

Typical Applications

  • Improve power factor for motors, compressors, and welding equipment in industrial plants.
  • Voltage stabilization in transmission and distribution networks for utilities.
  • Reduce electricity bills by minimizing reactive demand and avoid penalties.
  • Support voltage stability in wind and solar farms.
  • Installed as fixed or switched banks to provide reactive compensation dynamically.
  • In substation to improve voltage at tail end of the line.

Technical Specifications

Parameter Specification
Rated Voltage 440- 40kV
Frequency 50 Hz/60Hz
Phases 1 PH/ 3PH
Container CRCA/SS 409/SS304
Standards IS 13925, IEC 60871-1:2014
Configuration 1-Φ/1B, 1-Φ/2B, 3-Φ/Δ/3B, 3Φ/Y/3B, 3Φ/Y/4B
Protection Level Up to 170 kVp BIL
Installation Indoor / Outdoor

APIL Value Proposition

The Shunt power capacitor manufactured by Akanksha Power & Infrastructure Ltd. As per the customer requirement and application, highly used for reactive power compensation which improves power factor and voltage stabilization of the system.

Marketing Pitch

"APIL's Shunt Power Capacitors provides Power up efficiency and shunt capacitors deliver stability, savings, and stronger grids which improves Power Quality."

PULSE CAPACITOR

Pulse Power Application

APIL’s Pulse capacitor is APP (All Polypropylene) type non-self-healing and oil impregnated. This Pulse capacitor is a specialized capacitor designed to deliver short-duration, high-energy pulses in applications requiring rapid discharge and recharge cycles. Unlike conventional capacitors, they are optimized for high peak currents, low inductance, and minimal losses, making them essential in pulsed power systems.

Key Features

  • High peak current capability which handles extremely high discharge currents (often several kA) without degradation.
  • Low Equivalent Series Resistance (ESR) and Equivalent Series Inductance (ELR) which ensures minimal energy loss and fast pulse response.
  • Typically ranges from 1 kV to 100 kV depending on application.
  • Uses polypropylene for high dielectric withstand and low losses.
  • Can withstand millions of charges–discharge cycles without failure.
  • Container of pulse capacitors are of stainless steel.
  • Highly used for impulse test setup & pulse power system.

Principle of Operation

The pulse capacitor operation principle is rapid energy storage and instantaneous discharge. It is designed to accumulate electrical energy over a short charging period and release it in a powerful, controlled pulse when triggered which enabling high-energy bursts for applications like radar, lasers, and pulsed power systems.

Typical Applications

  • High-voltage experiments labs, impulse testing, fusion research and particle physics labs.
  • Use in defence services like Radar, pulsed lasers and electromagnetic weapons.
  • Plasma generation, welding, and particle accelerators.
  • Use in medical equipment like MRI machines, defibrillators and X-ray systems.
  • Can be use as short-term storage for rapid energy release.
  • Use in civil, defence, medical, commercial applications.

Technical Specifications (Typical)

Parameter Specification
Charging Voltage 100kV DC
Tan delta < 2 x 10-4
Typical Charging 15s
Typical Discharge 10 to 100 μs
Container Stainless steel 304 grade
Impregnant Non PCB Oil
Installation Indoor oil immersed

APIL Value Proposition

The Pulse capacitor manufactured by Akanksha Power & Infrastructure Ltd. Using polypropylene film immersed in non-PCB oil for high dielectric withstand and low losses which can withstand numbers of charges–discharge cycles without failure.

Marketing Pitch

"APIL's Pulse Capacitors delivering precision pulse with withstand capacity of multiple high energy charge discharge operations and enhance the equipments used in various crucial sectors ."

SURGE CAPACITOR

Shunt Reactive Power

APIL’s Surge capacitor is a protective component used in high-voltage systems to absorb and smooth transient overvoltage caused by switching operations or lightning strikes. This can be used in fixed indoor/outdoor as per design. This capacitor is APP (All Polypropylene) type non-self-healing and oil impregnated.

Key Features

  • Surge Capacitor unit is designed up to system of 33kV (designed as per requirement)
  • The low inductance design ensures fast response to high-frequency transients.
  • Designed at Tan delta ≤ 2 x 10-4
  • Limits steep voltage wavefronts during switching or lightning surges which gives transient suppression.
  • Provides fast transient response and voltage stabilization.
  • Provided with external fuse design and stainless-steel case.
  • Use dead soft annealed electrode and polypropylene for high withstand capacity.
  • Non-Self-healing design with oil impregnated.
  • Natural air-cooled design and temperature category up to -25/D.
  • Suitable for indoor and outdoor applications.

Principle of Operation

A surge capacitor operates on the principle of transient voltage absorption and waveform smoothing. It works by momentarily storing the surge energy and releasing it gradually, thereby protecting connected equipment from steep voltage spikes caused by switching or lightning.

Typical Applications

  • Protects against voltage spikes during opening and closing operation of vacuum switch or breaker.
  • Prevents insulation of motors and generators damaging from switching surges.
  • Reduce transient stresses on transformer windings.
  • Enhances protection and reliability of medium-voltage switchgear and APFC panels.
  • Use at substations and power plant for surge protection due to lightning.

Technical Specifications

Parameter Specification
Rated Voltage Up to 33kV
Frequency 50 Hz/60Hz
Phases 1 PH/ 3PH
Container CRCA/SS 409/SS304
Standards IEC 60871-1:2014.
Configuration 1-Φ/1B, 3-Φ/3B to ground
Protection Level Up to 170 kVp BIL
Installation Indoor / Outdoor

APIL Value Proposition

The Surge capacitor manufactured by Akanksha Power & Infrastructure Ltd. As per the customer requirement and application, highly used for protecting connected equipment from steep voltage spikes caused by switching or lightning.

Marketing Pitch

"APIL's surge capacitors provides shield to system for switching transient, voltage spikes and protect equipment's like motor, generator, transformer, capacitors connected in the system."

Specifications

  • Power quality analyser in accordance with IEC 61000-4-30 Class A
  • Comprehensive energy management solutions, with a focus on ISO 50001 certification and a range of products and services to optimize energy consumption and efficiency.
  • Software platform enables comprehensive energy monitoring, analysis, and reporting, supporting various functions like energy data management, network analysis, and automation.
  • Offers a range of measurement devices for monitoring energy consumption, including Power Quality Analysers.

Transfer Ladle

  • Application :

    Mixer of mouth & leap area.

  • Service Temp. :

    1500°C Max.

  • Base Material:

    LF Bauxite, Sillimanite and high purity cement

  • Special Features:

    Very high strength & replaces back up lining.

  • Application :

    Mixer of mouth & leap area.

  • Service Temp. :

    1600°C Max.

  • Base Material:

    LF Bauxite, Sillimanite, WFA and high purity cement.

  • Special Features:

    Very high strength & volume stability.

  • Application :

    Mixer of mouth & leap area.

  • Service Temp. :

    1600°C Max.

  • Base Material:

    LF Bauxite, BTA, WFA and high purity cement.

  • Special Features:

    Very low rebound loss & excellent resistance to Corrosion & Erosion to metal.

Our Trusted Clienteles